Power Management Unit with NMS
 



90-300V L-N (155-520 V L-L) Wide Range Input
Output 220 V +/- 5/10% through Static stabaliser (Tr<400V/us).
Detailed Display system using 20 x 4 LCD, 3 x 3 Seven Segment and LEDs
Inbuilt AMF/Transfer Switch for any make of DG set.
DG protection and exhaustive parameter settings options
Inbuilt Auto healthy phase selector
Galvanic isolation of 6KV on utility power supply.
Encapsulated Class B Lightning protection and Class C Surge Protection
Single/Multi Static Line Conditioner configurations
Fire and Door alarm panel along with other infra alarms
AC Distribution as per customer specifications
Air conditioner controller on customer request
Serial port for data transfer and field settings
Serial port for data transfer and field settings
Serial port for data transfer and field settings
   




13 potential free contacts PLUS 5 high current contacts
Optional Fuel management system
Full Energy management for Mains & DG
Comes in Stand alone powder coated mechanical cabinet
Double DG Provision is available

 
 
General Description of VNT PMU
 
I
Description
Specification
structure
1
Capacity
5-30KVA (Single/Modular design)
2
Mechanical

Stand alone, powder coated, 19” CNC Fabricated rack

3
Thickness
1.6mm thick CRC sheet
4
IP Protection
IP 21 for Indoor (IP43/IP45/ IP 55 versions also available for outdoor application)          
II
Safety and environmental
5
Tests
Compliance with environmental and safety requirements for CE, tested under Class 1,2 and3 tests as per IEC 61643 -2005,ANSI IEEE62.41,62.41 EN61000
6
Safety
As per IEC 60950 safety standards
7
MTBF
>72000 hrs
8
Impulse Immunity Level (Uw)
>=12KV as per IEC 60664
III
Central processing unit
9
Micro Controller
TCP/IP/CAN enabled high speed microcontrollerduly protected as per IEC 62305-4,ANSI IEEE62.41,UL1449 with in built energy managementfeatures
10
RTC
REAL TIME CLOCK provided in the system (User settable)
11
Alarm Logs
Min 100 logs with date and time stampDownloading data from other
12
RS 232 Port(s)
Multiple RS232 ports interface to interface with PC for settings and intelligent controllers over CAN like solar systems, fuel cells etc. to carry data to a central station using single SIM card
13
Digital Spare Inputs
Available
14
NMS
pasward protected central management systemwith MIS all over country/region of all sites through SMS and SMSD facility forcustomer selected user
IV
LCU with Inbuilt isolation transformer - (Single LCU and Multi LCU configurations available)
15
Type
Password protected Central Management Systemwith MIS all over country/region sites GPRSAlarm SMS and SMSD facility for customer selected user phone numbers
16
Rated input voltage
range 155-520V input L-L
17
Rated Output Voltage
220 V +/- 10%(Ph-N) (Please check for other available tailered ranges with us)
18
Input Frequency Range
47-53 Hz with Under and Over Frequency cutoff
19
In-put Power factor at100% load@415V(Ph-Ph) i/p & 215V(LN)`o/p
>0.99(50 to 100% Load)
20
Out-put Power factor at 00% load@415V i/p & 215Vo/p
>0.99
21
Efficiency at full load & min/max i/p range
>= 97% (50 to 100% Load)
22
Dynamic response time
400V/us (approx)
23
Response Time
less than half cycle of 50Hz AC
24
Auto Phase Selector
Optional 3 in 2 out OR 3 in 1 out phase selector Voltage correction section
 
V Protections  
25 Input Utility Mains circuit breaker (MCB/MCCB) and DG MCB
26 Voltage protection levels-2 at input

High Voltage Disconnect at safe high voltagphase-phase with a delay of 10 milliseconds, Low Voltage Disconnect at safe low voltage after 5 seconds

27 Voltage protection levels-2 at output Provided at set voltage in 10 seconds Low voltage Disconnect at safe low voltage after 5 seconds
28 Insulation >1000 megaohms
29 Inter winding capacitance <10 nF
30 Input/Output isolation 6KV
31 Winding Double wound with copper foil shielding I/p O/p Nuetral Isolation
32 Inrush Current 110 A for 10 Seconds
33 Temperature (-5 to 55 deg)
34 Humidity RH 95%
VI Lightning and Surge Protection  
RADAX Flow Class 1 (100KA 10/350 micro sec) protection as per IEC 62305-4
energy coordinated with stage 2 protection (40KA,8/20 micro sec)
VII Auto Genset Control System (AMF)
35 DG Trip Protection (Safety with Alarms)
A Low lube oil
B Low fuel level
C Over load (Adjustable depending on DG capacity) (>110% to be set
D Voltage Protection. (a) HVD & LVD- +-5V above/below the range
E HCT/HWT
F Over speed
G Alternator fault
36 Delays
A All safety delays of mains DG changeover, interval between start attempts etcare incorporated
37 Battery charger & DG controller unit
A SMPS charger with auto float cum charge mode with LED indications
B Manual start, stop and reset
C DC V/I meter with selector switch
D Reverse Battery protection
E Interlocking to DG Charge alternator
VIII General
38 General items
A ACDB As per customer requirement
B Aviation lamp controller, 48V DC 
C Room temperature sensor
D Potential free contact -2A/24V/48V DC or suitable
E FIRE/SMOKE SENSOR: Double Ionisation type fire sensor with potential freecontact for fire/smoke alarm
F DG and Mains Run Hour counter
G BTS Battery and Temperature monitoring for intelligent Start of DG after mainsfailure
NOTE: PMU can be customised as per customer's requirement for any features including voltage ranges