| V |
Protections |
|
| 25 |
Input |
Utility Mains circuit breaker (MCB/MCCB) and DG MCB |
| 26 |
Voltage protection levels-2 at input |
High Voltage Disconnect at safe high voltagphase-phase with a delay of 10 milliseconds, Low Voltage Disconnect at safe low voltage after 5 seconds
|
| 27 |
Voltage protection levels-2 at output |
Provided at set voltage in 10 seconds Low voltage Disconnect at safe low voltage after 5 seconds |
| 28 |
Insulation |
>1000 megaohms |
| 29 |
Inter winding capacitance |
<10 nF |
| 30 |
Input/Output isolation |
6KV |
| 31 |
Winding |
Double wound with copper foil shielding I/p O/p Nuetral Isolation |
| 32 |
Inrush Current |
110 A for 10 Seconds |
| 33 |
Temperature |
(-5 to 55 deg) |
| 34 |
Humidity |
RH 95% |
| VI |
Lightning and Surge Protection |
|
|
RADAX Flow Class 1 (100KA 10/350 micro sec) protection as per IEC 62305-4 |
|
energy coordinated with stage 2 protection (40KA,8/20 micro sec) |
| VII |
Auto Genset Control System (AMF) |
| 35 |
DG Trip Protection (Safety with Alarms) |
| A |
Low lube oil |
| B |
Low fuel level |
| C |
Over load (Adjustable depending on DG capacity) (>110% to be set |
| D |
Voltage Protection. (a) HVD & LVD- +-5V above/below the range |
| E |
HCT/HWT |
| F |
Over speed |
| G |
Alternator fault |
| 36 |
Delays |
| A |
All safety delays of mains DG changeover, interval between start attempts etcare incorporated |
| 37 |
Battery charger & DG controller unit |
| A |
SMPS charger with auto float cum charge mode with LED indications |
| B |
Manual start, stop and reset |
| C |
DC V/I meter with selector switch |
| D |
Reverse Battery protection |
| E |
Interlocking to DG Charge alternator |
| VIII |
General |
| 38 |
General items |
| A |
ACDB |
As per customer requirement |
| B |
Aviation lamp controller, 48V DC |
| C |
Room temperature sensor |
| D |
Potential free contact -2A/24V/48V DC or suitable |
| E |
FIRE/SMOKE SENSOR: Double Ionisation type fire sensor with potential freecontact for fire/smoke alarm |
| F |
DG and Mains Run Hour counter |
| G |
BTS Battery and Temperature monitoring for intelligent Start of DG after mainsfailure |
| NOTE: |
PMU can be customised as per customer's requirement for any features including voltage ranges |